User’sManualIM 05D01D12-41EModels UT351/UT321Digital Indicating ControllersUser’s ManualIM 05D01D12-41E6th Edition
1-2<Toc> <1. Installation>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-001.2 How to InstallNOTETo install the controller, select a location
<Toc> <1. Installation>1-3IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 External Dimensions and Panel Cutout Dimensions(25)(53)[(N-1)96
1-4<Toc> <1. Installation>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 How to InstallCAUTIONTurn off the power to the controller before
<Toc> <1. Installation>1-5IM 05D01D12-41E 6th Edition: Mar. 25, 2005-001.3 How to Connect WiresCAUTION1) Before carrying out wiring, turn
1-6<Toc> <1. Installation>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00● Cable Specifications and Recommended CablesPurpose Name and Manu
<Toc> <1. Installation>1-7IM 05D01D12-41E 6th Edition: Mar. 25, 2005-001.4 Hardware SpecificationsPV Input Signals• Number of inputs: 1 (
1-8<Toc> <1. Installation>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00Retransmission OutputEither PV, target setpoint, or control output
<Toc> <1. Installation>1-9IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00Contact Inputs• Purpose: Selection between target setpoints or Aut
1-10<Toc> <1. Installation>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00Safety and EMC Standards• Safety: Complies with IEC/EN61010-1 (CE
<Toc> <1. Installation>1-11IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00• Panel cutout dimensions:UT351 920+0.8 (W) 920+0.8 (H) mmUT3
1-12<Toc> <1. Installation>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00• Relay contact alarm output terminals: Not isolated between rela
<Toc> <1. Installation>1-13IM 05D01D12-41E 6th Edition: Mar. 25, 2005-001.5 Terminal Wiring DiagramsNOTEDo not use unassigned terminals a
1-14<Toc> <1. Installation>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 UT351 Standard Type (Model UT351-0 or UT351-3)12Relay contact
<Toc> <1. Installation>1-15IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 UT351 Heating/Cooling Type (Model UT351-2)Heating-side control
1-16<Toc> <1. Installation>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 UT321 Standard Type (Model UT321-0 or UT321-3)12Relay contact
<Toc> <1. Installation>1-17IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 UT321 Heating/Cooling Type (Model UT321-2)Heating-side control
Blank Page
<Toc> <2. Initial Settings>2-1IM 05D01D12-41E 6th Edition: Mar. 25, 2005-002. Initial SettingsThis chapter describes examples of setting
2-2<Toc> <2. Initial Settings>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-002.1 Names and Functions of Front Panel Parts
<Toc> <2. Initial Settings>2-3IM 05D01D12-41E 6th Edition: Mar. 25, 2005-002.2 Setting PV Input Type (Setting First at Power-on)NOTE• The
<Toc> <Rev>iIM 05D01D12-41E 6th Edition: Mar. 25, 2005-00IntroductionThank you for purchasing the UT351/UT321 digital indicating controlle
2-4<Toc> <2. Initial Settings>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-003.Press the SET/ENT key once to register therequired setpoint.
<Toc> <2. Initial Settings>2-5IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Instrument Input Range CodesInput TypeSelect the unit from t
2-6<Toc> <2. Initial Settings>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-002.3 Changing PV Input TypeThe following operating procedure de
<Toc> <2. Initial Settings>2-7IM 05D01D12-41E 6th Edition: Mar. 25, 2005-009.Press the SET/ENT key once to register thesetpoint.PVMANA/MS
2-8<Toc> <2. Initial Settings>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-002.4 Setting Control Output TypeThe following operating procedu
<Toc> <2. Initial Settings>2-9IM 05D01D12-41E 6th Edition: Mar. 25, 2005-009.Press the SET/ENT key once to register thesetpoint.PVMANA/MS
2-10<Toc> <2. Initial Settings>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-005.Press the SET/ENT key once to display themenu “FUNC”.PVMANA
<Toc> <2. Initial Settings>2-11IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 List of Alarm TypesThe table below shows the alarm types an
2-12<Toc> <2. Initial Settings>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00Note 1: The fault diagnosis output turns on in case of input
<Toc> <2. Initial Settings>2-13IM 05D01D12-41E 6th Edition: Mar. 25, 2005-002.6 Setting the PV Display Color Changing Function“Active Col
ii<Toc> <Rev>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Safety PrecautionsThe following symbol is indicated on the controller to ensur
2-14<Toc> <2. Initial Settings>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-002.7 Setting the High Limit and Low limit for PV ColorChangeTh
<Toc> <3. Operations>3-1IM 05D01D12-41E 6th Edition: Mar. 25, 2005-003. OperationsThis chapter describes key entries for operating the co
3-2<Toc> <3. Operations>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Operating Displays for a Heating/Cooling Controller● SP DisplayThe
<Toc> <3. Operations>3-3IM 05D01D12-41E 6th Edition: Mar. 25, 2005-003.2 Setting Target Setpoint (SP)The following operating procedure de
3-4<Toc> <3. Operations>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-003.3 Performing/Canceling Auto-tuningAuto-tuning should be carried ou
<Toc> <3. Operations>3-5IM 05D01D12-41E 6th Edition: Mar. 25, 2005-005.Press the SET/ENT key once to register thesetpoint. (This starts a
3-6<Toc> <3. Operations>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-007.Press the or key to display therequired setpoint.PVMANA/MSPAL1
<Toc> <3. Operations>3-7IM 05D01D12-41E 6th Edition: Mar. 25, 2005-003.Press the SET/ENT key twice to display theparameter “A1”.PVMANA/MS
3-8<Toc> <3. Operations>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-003.Press the SET/ENT key several times todisplay the parameter “SP.NO
<Toc> <3. Operations>3-9IM 05D01D12-41E 6th Edition: Mar. 25, 2005-003.8 Switching between AUTO and MANNOTEIf AUTO and MAN have been swit
<Toc> <Rev>iiiIM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Regarding Protection, Safety, and Prohibition Against UnauthorizedModificatio
3-10<Toc> <3. Operations>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-003.9 Manipulating Control Output in ManualOperationNOTEControl outpu
<Toc> <3. Operations>3-11IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00● Controller Behavior and Control Output Manipulation when the Dead
Blank Page
<Toc> <4. Troubleshooting and Maintenance>4-1IM 05D01D12-41E 6th Edition: Mar. 25, 2005-004. Troubleshooting and Maintenance4.1 Troublesh
4-2<Toc> <4. Troubleshooting and Maintenance>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Errors at Power onThe following table shows e
<Toc> <4. Troubleshooting and Maintenance>4-3IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 If a Power Failure Occurs during Operation● M
4-4<Toc> <4. Troubleshooting and Maintenance>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Troubleshooting when the Controller Fails to
<Toc> <4. Troubleshooting and Maintenance>4-5IM 05D01D12-41E 6th Edition: Mar. 25, 2005-004.2 MaintenanceThis section describes the clean
4-6<Toc> <4. Troubleshooting and Maintenance>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-004.2.3 Attaching Terminal CoverWhen a terminal c
<Toc> <4. Troubleshooting and Maintenance>4-7IM 05D01D12-41E 6th Edition: Mar. 25, 2005-002.With the cover properly folded, fit its top a
Blank Page
4-8<Toc> <4. Troubleshooting and Maintenance>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-004.2.5 Replacing Control Output RelaysThis subse
<Toc> <4. Troubleshooting and Maintenance>4-9IM 05D01D12-41E 6th Edition: Mar. 25, 2005-004.Hold the bezel and pull it along with the int
4-10<Toc> <4. Troubleshooting and Maintenance>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-007.Insert the internal unit into the housing.Ap
<Toc> <5. Parameters>5-1IM 05D01D12-41E 6th Edition: Mar. 25, 2005-005. ParametersThis chapter contains a parameter map as a guideline fo
5-2<Toc> <5. Parameters>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00A3A1LLA2PIDSCATSP.NODNRBSFLUPROLOHDRHHC2HB2HB1PCCLPCCHHC1ORHORB1.SPO
<Toc> <5. Parameters>5-3IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00STUPSETDisplayed when voltage input.Displayed when IN=TC.AL2SPLSPHPC
5-4<Toc> <5. Parameters>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-005.2 Lists of Parameters* Parameters relating to PV or setpoints shou
<Toc> <5. Parameters>5-5IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00Parameter SymbolName of Parameter Setting Range and Description Init
5-6<Toc> <5. Parameters>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00● PID-related ParametersThe following parameters are displayed when
<Toc> <5. Parameters>5-7IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Auto-tuningAuto-tuning is a function with which the controller aut
Toc-i<Int> <Rev>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00CONTENTSModel UT351/UT321Digital Indicating ControllersUser’s ManualIM 05D01D
5-8<Toc> <5. Parameters>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Hysteresis (for Target Setpoints (On-Off Control) and Alarm Setpoi
<Toc> <5. Parameters>5-9IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00The figure below shows an example when the Target Setpoint Number (S
5-10<Toc> <5. Parameters>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Setup Parameters● Control Function-related ParametersAlarm-1 type
<Toc> <5. Parameters>5-11IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00PID control mode0: Standard PID control (with output bump at SP ch
5-12<Toc> <5. Parameters>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00● Precautions for Use of Heater Burnout Alarm(1) The heater burnout
<Toc> <5. Parameters>5-13IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00● Input-/Output-related ParametersHeating/coolingtype: 4The followi
5-14<Toc> <5. Parameters>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00DI function selection 1(DIS)Retransmission output type1: PV, 2: SP
<Toc> <5. Parameters>5-15IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Functions of Active Color PV DisplayThis part describes the funct
5-16<Toc> <5. Parameters>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00Set high limit “70°C” for PCCH, and low limit “20°C” for PCCL.PV di
<Toc> <5. Parameters>5-17IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 External RJCThe external RJC is not a compensation function built
<Int> <Rev>IM 05D01D12-41EToc-ii6th Edition: Mar. 25, 2005-005. Parameters...
5-18<Toc> <5. Parameters>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Useful Operating Displays (SELECT Display)Registering frequently
<Toc> <5. Parameters>5-19IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Heating/Cooling Control (for a Heating/Cooling Controller Only)In
5-20<Toc> <5. Parameters>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Cycle TimeA cycle time can only be set if the type of control out
<Toc> <6. Function Block Diagram and Descriptions>6-1IM 05D01D12-41E 6th Edition: Mar. 25, 2005-006. Function Block Diagram andDescriptio
6-2<Toc> <6. Function Block Diagram and Descriptions>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Function Block Diagram for Standard T
<Toc> <6. Function Block Diagram and Descriptions>6-3IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Function Block Diagram for Heating/Co
6-4<Toc> <6. Function Block Diagram and Descriptions>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00Functions and Parameters for “Standard
<Toc> <6. Function Block Diagram and Descriptions>6-5IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Contact InputChanging the setpoint of
6-6<Toc> <6. Function Block Diagram and Descriptions>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Target Setpoint and PIDIt is possible
<Toc> <6. Function Block Diagram and Descriptions>6-7IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Control OutputControl output (OUTPUT1
<Toc> <1. Installation>1-1IM 05D01D12-41E 6th Edition: Mar. 25, 2005-001. InstallationThis chapter describes installation, wiring, and ot
6-8<Toc> <6. Function Block Diagram and Descriptions>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00 Retransmission OutputPV, target setpo
i<Int> <Toc>IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00Revision Information● Title : Model UT351/UT321 Digital Indicating Controllers Us
Blank Page
YOKOGAWA ELECTRIC CORPORATIONNetwork Solutions Business Division2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JAPANPhone: +81-422-52-7179 Facsimile: